#1054 new bug

1-stage AC heating mode flow rate is 2x what it should be

Reported by: ewilson Owned by:
Priority: high Component: General
Version: 0.1 Waiting on Others Keywords:
Cc: shorowit, jwinkler

Description

Energy Plus error? Seen in hourly output when dividing fan flow rate by runtime fraction. Cooling flow is as expected. 2-stage flow rates are as expected.

Affects duct leakage. 36% increase in heating duct leakage when going from 1 stage SEER 16 to 2 stage SEER 16, due to much decreased runtime fractions (~50%) during heating mode.

Change History (4)

comment:1 Changed 2 years ago by shorowit

  • Version changed from Future to 2.6.0.2

comment:2 Changed 2 years ago by shorowit

Is this still a problem using E+ 8.6?

comment:3 Changed 22 months ago by ewilson

Still a problem using E+ 8.6. I'll prepare an EnergyPlus bug report.

comment:4 Changed 22 months ago by ewilson

  • Version changed from 2.7.0.0 to 0.1 Waiting on Others